Active job

Quotation to bring building to compliance standard

Job description

Fire Safety Inspections
Waipa

Work has been identified to bring our building into compliance with fire safety standards Quotations welcome: 1/Security relay not mounted in panel. Battery requires replacing (12v 7 A/H) 4 x smoke detectors Zone C office area within 1 metre of aircon outlet. Entrance lobby requires a heat detector to be installed. 1 x smoke detector required by Fire Alarm panel due to spacing of detectors Zone A warehouse area requires additional heat detectors to be installed due to the C chanel beams on roofline.additional detectors installed. 2/ Heats in Zone A warehouse are incorrectly spaced. Some heats are more than 5m off walls and 7m centers. Petrusions are also 200mm deep and detectors requires 2/3 spacings. Note: several heats will need to be installed to comply. 3/1x smoke detector required between smoke detectors by FAP as they are 12m apart. 4/ 4 x smoke detectors in Zone C office area within 1m of ac outlets. 5/ No detection in entrance lobby